Phoenix Cooling Load Calculator (Manual J Estimate)

Estimates the residential cooling load for Phoenix, AZ using a simplified Manual J methodology. Enter your home's characteristics to calculate the required AC tonnage and BTU/hr.

Home Dimensions

Envelope Construction

Windows & Doors

Infiltration & Ventilation

Internal Gains

Formulas Used

1. Conduction Load: Q = U × A × ΔT

  • U = overall heat transfer coefficient (BTU/hr·ft²·°F)
  • A = surface area (ft²)
  • ΔT = 110°F − 75°F = 35°F (Phoenix design outdoor − indoor setpoint)

2. Solar Gain: Qsolar = SHGC × Awindow × Ipeak × CForient × CFshade

  • Ipeak = 250 BTU/hr·ft² (Phoenix peak west-facing, ASHRAE)
  • SHGC = Solar Heat Gain Coefficient of glazing

3. Infiltration (Sensible): Qinf = 1.1 × CFM × ΔT  |  CFM = (ACH × Volume) / 60

4. Infiltration (Latent): Qlat = 0.68 × CFM × ΔW  |  ΔW = 28 gr/lb (Phoenix)

5. Internal Gains: Occupants (250 BTU/hr sensible + 200 BTU/hr latent each) + Lighting (W × 3.412) + Appliances

6. Total Load: Qtotal = Qconduction + Qsolar + Qinfiltration + Qinternal + Qlatent

7. Tonnage: Tons = Qtotal / 12,000 BTU/hr per ton

Assumptions & References

  • Phoenix, AZ ASHRAE 0.4% cooling design dry-bulb: 110°F (ASHRAE Fundamentals Handbook, Chapter 14)
  • Indoor design temperature: 75°F (ACCA Manual J, 8th Edition standard)
  • Design temperature difference (ΔT): 35°F
  • Phoenix design grains difference: 28 gr/lb (ACCA Manual J Table 1, Phoenix, AZ)
  • Peak solar irradiance (west-facing vertical): 250 BTU/hr·ft² (ASHRAE HOF Table)
  • Sensible heat factor for air: 1.1 BTU·min/(hr·CFM·°F)
  • Latent heat factor for air: 0.68 BTU·min/(hr·CFM·gr/lb)
  • Occupant sensible gain: 250 BTU/hr; latent: 200 BTU/hr (ASHRAE 62.2, sedentary activity)
  • Lighting conversion: 1 W = 3.412 BTU/hr
  • Wall area estimated from square footprint assumption per story
  • Ceiling area = ground floor area ÷ number of stories (top floor only)
  • Manual J recommends equipment sized within +15% / −0% of calculated load (ACCA Manual S)
  • This tool does not account for duct losses, mechanical ventilation (ERV/HRV), or radiant barriers
  • References: ACCA Manual J 8th Ed., ASHRAE Fundamentals 2021, IECC 2021 Climate Zone 2B (Phoenix)